LEAK DETECTION DESIGN
BMI Press fittings are made with a Leak Detection Design, providing fast and easy identification of unpressed connections during the pressure testing process in any installation angle possible.
The design feature provides a path for liquids and/or gases from inside the system past the sealing element of an unpressed connection.
When pressed according to instructions, the Leak Detection Design feature is neutralized, creating a leak-proof, permanent connection.
Unpressed connections are located by pressurizing the system with air or water. When testing with water the suggested pressure of 15 to 85 psi maximum. (Test with air can be dangerous, manufacturer
recommend testing compressed air at ½ to 45 psi maximum).
Following a successful test, the system may be pressure tested up
to 600 psi maximum for water and 200 psi maximum for air,
depending on local code requirements.